6.2 GROUND CONNECTION – Connect the ground wire (earth) to any available green Ground Screw.
The two Ground Screws are located near Terminal Block TB1. Be sure the motor is also properly
grounded. See Figure 10, on page 18, and Figure 11, above.
6.3 MOTOR CONNECTION – Connect the motor to Terminal Block TB1 Terminals “U”, “V”, “W”. See
Figur
e 10, on page 18, and Figure 11, above. Be sure the motor is properly grounded. Motor cable
length should not exceed 100 ft. (30 m) – special reactors may be required – consult our Sales
Department. Be sure Function No. 0.01 is set to the corresponding Motor Nameplate Current.
Note: If the motor does not rotate in the desired dir
ection, either: 1. Reverse any two motor leads
(with AC line disconnected and motor stopped). or 2. Use the FWD/REV Key
. or 3. Use Function
No. 1.02 to reprogram the forward and r
everse direction.
6.4 MULTI-FUNCTION OUTPUT RELAY CONNECTION – The Multi-Function Output Relay Contacts
are located at TB2, as shown in Figure 12. The Multi-Function Output Relay is factory pro-
grammed to function as a “Run” r
elay (Function No. 5.00 set to “0000”). When the drive is put into
the Run Mode, the r
elay contacts will change state (the Normally Open (N.O.) contact will close
and the Normally Closed (N.C.) contact will open). See Table 5.
19
Normally Closed
Relay Common
Normally Open
Output Contacts
KBDA-27D, 29, 45, 48
NCNO
TB2
COM
Normally Closed
Relay Common
Normally Open
Output Contacts
KBDA-24D
NCNO
TB2
COM
Ground 3-Phase, 50/60 HzMotor
(Earth) AC Line Input
VU L3L2W L1
208/230, 400/460 Volt
TB1
MOTOR AC LINE
Ground
Single-Phase, 50/60 Hz
(Earth)
208/230 Volt
L2
L1 L3
Wire the single-phase AC line input
to Terminals "L1" & "L2", as shown below.
Model KBDA-29 Only
AC Line Input
Notes: 1. Model KBDA-29 is rated for 2 HP maximum with single-phase AC line input and 3 HP maximum with 3-phase AC line input.
2. Models KBDA-29, 45, 48 contain AC Line Phase Loss Detection. (Model KBDA-29: when used on 3-phase AC line input set for 7.0 Amps
or higher (3 HP (2.25 kW)).
FIGURE 11 – MODELS KBDA-29
1
,45
2
,48
2
AC LINE INPUT, MOTOR, AND GROUND CONNECTIONS
FIGURE 12 – MULTI-FUNCTION OUTPUT RELAY CONTACTS
TABLE 5 – MULTI-FUNCTION OUTPUT RELAY “RUN” AND “FAULT” RELAY OPERATING MODES
Drive Operating Condition
Function 5.00 Set to “0000” Function 5.00 Set to “0001”
“Run” Relay Mode “Fault” Relay Mode
N.O. Contact N.C. Contact N.O. Contact N.C. Contact
Power Off Open Closed Open Closed
Power On (Stop Mode) Open Closed Closed Open
Run Mode Closed Open Closed Open
All Faults Open Closed Open Closed