INSTALLATION AND OPERATION MANUAL
KBMK SERIES
Adjustable Frequency Drives
for 1/8 HP thru 1 HP 3-Phase AC Motors Rated 208 – 230 VAC, 50/60 Hz
NEMA-1 / IP-40
Operate from 115* and 208/230 Volt 50/60 Hz AC Line
Variable Speed / Soft-Start with Electronic Motor Overload Protection
1
*IMPORTANT
This drive is factory set for:
1. 60 Hz Motors.
For 50 Hz motors, see Figure 12, on page 16.
2. 208/230 Volt AC Line Input.
For 115 Volt AC line input, see Section 7, on page 14.
See Safety Warning, on page 5.
I
LISTED
IND. CONT.
EQ. – 70ZA
2
RoHS
This Manual Covers Models KBMK-24D and KBMK-24DF
2
The information contained in this manual is intended to be accurate. However, the
manufacturer retains the right to make changes in design which may not be included herein.
Notes: 1. UL approved as an electronic overload protector for motors. 2. Model KBMK-24DF contains a built-in
AC line Class A RFI (EMI) filter which meets CE Council Directive 89/336/EEC Industrial Requirement. For Class
B Residential Requirement, install the KBRF-300 RFI (EMI) Filter (Part No. 9484).
Automation and Control
COPYRIGHT © 2008 KB Electronics, Inc.
(see back cover)
Vue de la page 0
1 2 3 4 5 6 ... 52 53

Résumé du contenu

Page 1 - KBMK SERIES

INSTALLATION AND OPERATION MANUAL KBMK SERIES Adjustable Frequency Drives for 1/8 HP thru 1 HP 3-Phase AC Motors Rated 208 – 230 VAC, 50/60 Hz NEM

Page 2 - TABLE OF CONTENT3S

10 FIGURE 5 MECHANICAL SPECIFICATIONS 9.00.351094.3012627.91.105.101300.25.080.399.914X Ø4X Ø7.001781.7544.57.60.304.953.2081.35.101300.9524.10.9524.

Page 3

11 FIGURE 6 MAXIMUM ALLOWED MOTOR TORQUE VS. SPEED FIGURE 7 OPEN VENTILATED MOTOR WITH EXTERNAL FAN COOLING TEFC and Open VentilatedInverter Dutyan

Page 4

12 Be sure to properly fuse each AC line conductor that is not at ground potential. Do not fuse neutral or grounded conductors. A separate AC lin

Page 5

13 6.2 GROUND CONNECTION: Connect the ground (earth) wires from the AC line and motor to Terminal Block TB1 (Terminal "GND"). Be sure the

Page 6

14 7 AC LINE INPUT VOLTAGE SELECTION (JUMPER J1) Do not connect the AC line input until Jumper J1 is set for the proper input voltage being ap

Page 7

15 FIGURE 11 TYPICAL HI-POT TEST SETUP TESTRESETRETURNH. V.0mA 10mAVOLTAGEMAXZEROLEAKAGE 9 DRIVE OPERATION Before operating the drive, read Sect

Page 8

16 TABLE 6 KEYPAD DESCRIPTION Key Description Starts or Stops the drive. Changes motor direction. Up Key: Increases Output Frequency, Set Frequenc

Page 9

17 FIGURE 13 FLOW CHART TO PROGRAM MOTOR CURRENT FROM 3.6 AMPS TO 2.5 AMPS *The drive's factory setting of Motor Nameplate Current (Function No

Page 10

18 FIGURE 15 FLOW CHART TO PROGRAM ACCEL TIME VALUE FROM 1.5 SECONDS TO 120 SECONDS *The factory setting of Accel Time (Function No. 3.03) is "

Page 11

19 FIGURE 17 FLOW CHART TO PROGRAM THE DRIVE TO DISPLAY CUSTOM UNITS "012.0" Notes: 1. The factory setting of Display Mode (Function No. 4

Page 12

2 TABLE OF CONTENT3S Sections Page 1 Quick-Start Instructions...

Page 13

20 9.4 4-DIGIT DISPLAY: The 4-digit display provides readout of drive status, operating parameters, and faults. See Table 7, for the Digital Readout

Page 14

21 9.5 FAULT RECOVERY: The drive monitors many faults. See Function No. 1.05, on page 21, for restarting the drive after a fault has been cleared.

Page 15

22 PROGRAMMABLE FUNCTION SUMMARY LIST (Rev. 100.1) Model Software Revision Codes (Rev. 100.1) The Programmable Function List, on Pages 22 – 28, is A

Page 16

23 FUNCTION GROUP 1 – Run/Stop Mode Function No. Description Range/Code Factory Setting 1.00 * Run/Stop-Forward/Reverse Control 0000: Keypad 0001

Page 17

24 FUNCTION GROUP 2 – Frequency Control Function No. Description Code Factory Setting 2.00 * Frequency Control 0000: Keypad 0001: Built-In Potent

Page 18

25 FUNCTION GROUP 4 – Digital Display Modes Function No. Description Range/Code Factory Setting 4.00 Display Mode 0000: Frequency 0001: RPM (1) 00

Page 19

26 FUNCTION GROUP 6 – Drive Status and Reset Function No. Description Code Factory Setting 6.00 * Software Version ── ── 6.01 * Drive Horse

Page 20

27 FUNCTION GROUP 8 – Multi-Function Output Relays and Output Signal Operation (IODA Required) Function No. Description Range/Code Factory Setting

Page 21

28 FUNCTION GROUP 10 – Communication Mode (DIAC Required) Function No. Description Range/Code Factory Setting 10.00 * Assigned Communication Stat

Page 22

29 11 STATUS LEDs The drive's cover contains 8 LEDs which provide indication of the drive’s status and operating mode (Hz, PGM, LCL/REM, STOP,

Page 23

3 TABLE OF CONTENTS (CONTINUED) Figures Page 7 Open Ventilated Motor with External Fan Cooling...

Page 24

30 APPENDIX A – OPTIONAL IODA INPUT/OUTPUT MULTI-FUNCTION BOARD For detailed operation of the IODA, see the IODA Installation and Operation Instructi

Page 25

31 TABLE 9 IODA STATUS INDICATOR LED Condition Red STATUS LED Normal Operation Not Illuminated Communication Error1 Flashes 1 Second On and 1 Sec

Page 26

32 FIGURE 21 IODA TERMINAL BLOCK TB1 LAYOUT Common Terminals "8", "12", "14", "16", "18, "20"

Page 27

33 USING IODA MULTI-FUNCTION INPUT TERMINALS FOR REMOTE OPERATIONS A1. PRESET FREQUENCIES The drive is factory programmed for 7 Preset Frequencies,

Page 28

34 TABLE 14 PRESET FREQUENCY SELECTION Multi-Function Input Terminals to Select Preset Frequency Terminal 1 Terminal 2 Terminal 3 Function No. 7.

Page 29

35 TABLE 15 UP/DOWN FREQUENCY CONTROL PROGRAMMING Function No. Code/Range 1.00: Run/Stop-Forward/Reverse Control 0001: External Contacts 2.00: Frequ

Page 30

36 FIGURE 24 ACCEL/DECEL "2" CONENCTIONS A4. FORWARD/STOP AND REVERSE/STOP Remote Forward/Stop and Reverse/Stop operation can be perfo

Page 31

37 A5. EXTERNAL FAULT The Multi-Function Input Terminals can be used to "stop" the drive when a fault condition occurs elsewhere in the eq

Page 32

38 A6. RESET It is advisable to connect a momentary normally open switch or contact to Multi-Function Input Terminal "4". This allows the

Page 33

39 FIGURE 28 2-WIRE START/STOP CONNECTIONS 3-WIRE START/STOP SWITCH OR CONTACT CONNECTION 3-Wire Start/Stop requires momentary switches or contacts

Page 34

4 1 QUICK-START INSTRUCTIONS Important: You must read these simplified instructions before proceeding. These instructions are to be used as a refe

Page 35

40 OTHER FUNCTIONS AND FEATURES OF THE IODA A8. SIGNAL FOLLOWING An analog voltage (unidirectional or bidirectional), current, or PWM signal input

Page 36

41 FIGURE 31 ANALOG INPUT "1" AND "2" SIGNAL GAIN AND OFFSET WITH NEGATIVE SLOPE (HIGH-TO-LOW SIGNAL) (FUNCTION NO. 9.01 OR 9.06

Page 37

42 TABLE 23 ANALOG INPUT "1" SIGNAL VOLTAGE FOLLOWING PROGRAMMING Function No. Code/Range 2.00: Frequency Control 0002: Analog Signal 1 9.

Page 38

43 TABLE 24 ANALOG INPUT "2" ELECTRICAL RATINGS Parameter Specification Factory setting Voltage Range (Volts DC) 0 – ±2.5 thru 0 – ±25 0 –

Page 39

44 FIGURE 34 ANALOG OUTPUTS "1" AND "2" GAIN FIGURE 35 ANALOG OUTPUTS "1" AND "2" CONNECTIONS Jumpers J2 a

Page 40

45 ANALOG OUTPUT "1" Connect the auxiliary device signal input to Terminal "15" and the common to Terminal "16". ANAL

Page 41

46 FIGURE 36 REMOTE UNIDIRECTIONAL SPEED POTENTIOMETER CONNECTIONS MAX2 Trimpot and Jumper J1 *Use a jumper, between Terminals "5" and

Page 42 - as desired

47 BIDIRECTIONAL OPERATION WITH FORWARD/REVERSE: Connect the potentiometer to Terminals "9" (+5 Volts), "19" (Analog Input 1), an

Page 43

48 TABLE 31 MULTI-FUNCTION OUTPUT RELAY CONTACTS PROGRAMMING Function No. Code 8.00: Multi-Function Output Relay 1 0000: Run 0001: Fault 0002: Tar

Page 44

49 TABLE 32 MULTI-FUNCTION OPEN COLLECTOR OUTPUT PROGRAMMING Function No. Code 8.02: Multi-Function Open Collector Output 1 0000: Run 0001: Fault 00

Page 45

5 1.4 GROUND CONNECTION: Connect the ground wire (earth) to Terminal Block TB1 (Terminal "GND"), as shown in Figure 1, on page 4. 1.5 MOT

Page 46

50 – NOTES –

Page 47

51 – NOTES –

Page 48

LIMITED WARRANTY For a period of 18 months from the date of original purchase, KB Electronics, Inc. will repair or replace without

Page 49

RECONDITIONING THE BUS CAPACITORS If this drive has been in storage for over one year it is necessary to recondition the power supply bus capacitors.

Page 50 - – NOTES –

6 3 INTRODUCTION Thank you for purchasing the KBMK Adjustable Frequency Drive. KB Electronics, Inc. is committed to providing total customer sat

Page 51

7 3.2 PERFORMANCE FEATURES ▪ Power Start™ – Provides more than 200% starting torque which ensures startup of high frictional loads. ▪ Programma

Page 52

8 TABLE 3 GENERAL PERFORMANCE SAPECIFICATIONS Description Specification 115 Volt AC Line Input Voltage Operating Range (Volts AC) 115 (±15%) 208/23

Page 53

9 FIGURE 3 COVER LAYOUT I FIGURE 4 DRIVE LAYOUT