46
FIGURE 36
REMOTE UNIDIRECTIONAL SPEED POTENTIOMETER CONNECTIONS
MAX2 Trimpot
and Jumper J1
*Use a jumper, between Terminals "5" and "8", if a Start/Stop Switch or Contact is not
required.
BIDIRECTIONAL OPERATION WITH START/STOP (Use Analog Input "1" Only)
Connect the potentiometer to Terminals "9" (+5 Volts), "19" (Analog Input 1), and "10" (-5 Volts). Connect the
Start/Stop Switch or Contact to Terminal "5", which is factory set for N.O. Start ("0010"), and to any available
common terminal ("8", "12", "14", "16", "18", "20", "22"). See Table 29, for drive programming. See Figure 37,
for connections.
Operation: Close the Start/Stop Switch or contact to start the drive. At 50% rotation, the potentiometer is set
for zero speed. Rotating the potentiometer clockwise will increase motor frequency in the forward direction.
Rotating the potentiometer counterclockwise will increase motor frequency in the reverse direction. Open the
Start/Stop Switch or Contact to stop the drive.
TABLE 29
REMOTE BIDIRECTIONAL SPEED POTENTIOMETER PROGRAMMING
Function No. Code
1.00: Run/Stop-Forward/Reverse Control 0001: External Contacts
2.00: Frequency Control 0002: Analog Signal 1
7.04: Multi-Function Input Terminal 5 0010: N.O. Start*
9.03: Analog Input 1 Type 0001: Bidirectional
*Factory setting.
FIGURE 37
REMOTE BIDIRECTIONAL SPEED POTENTIOMETER CONNECTIONS
MAX2 Trimpot
and Jumper J1
*Use a jumper, between Terminals "5" and "8", if a Start/Stop Switch or Contact is no
t
required.